Determining the compact stations
Determining additional compact station components
11
143 |
Building Technologies
11 Determining the compact stations
The planning steps in this chapter apply to the compact ↑ stations and must be
performed separately for each station used of type FC2020, FC2030, FC2040,
FC2060, and FT2040.
You will find the planning of the FC2080 in a separate chapter.
You will find information about the country
specific availability of devices in
document 'Delivery Release'.
See also
2 Assembling the FC2080 [➙ 170]
11.1 Determining additional compact station components
Use the information in this chapter to determine the options for the individual
compact stations, FC2020, FC2030, FC2040, and FC2060. These details are
required to determine the power supply and batteries.
Use Required components Notes
Extra FDnet lines ● ↑ Loop extension (FDnet) FCI2003-A1
The loop extension is used on the
periphery board.
● ↑ Line card (FDnet/C-NET) FCL2001-
A1
The line card (FDnet/C-NET) is used
in the card cage and can be used in
the fire control panel FC2060.
Connecting collective
detectors
● Input/output module FDCIO223 for
connecting collective lines on the
FDnet
The input/output module FDCIO223
is connected on the FDnet line.
● Line card (collective) FCL2002-A1
The line card (collective) is used in
the card cage and can be used in the
fire control panels FC2030 and
FC2060.
Connecting MS9i detectors ● Line card (MS9i) FCL2003-A1
The line card (MS9i) is used in the
card cage and can be used in the fire
control panels FC2030 and FC2060.
Connecting AnalogPLUS
detectors
● Line card (AnalogPLUS) FCL2005-A1
The line card (AnalogPLUS) is used
in the card cage and can be used in
the fire control panels FC2030 and
FC2060.
Connecting interactive
detectors
● Line card (interactive) FCL2006-A1
The line card (interactive) is used in
the card cage and can be used in the
fire control panels FC2030 and
FC2060.
Connecting interactive Ex
detectors
● Line card (interactive Ex) FCL2007-A1
The line card (interactive Ex) is used
in the card cage and can be used in
the fire control panels FC2030 and
FC2060.
Additional programmable
inputs/outputs
● I/O card (programmable) FCI2008-A1
● Input/output modules FDCIO221,
FDCIO223, FDCIO224, FDCI221
The I/O card is used in the card cage
and can be used in the fire control
panels FC2030 and FC2060.