Planning the networking of the stations
SAFEDLINK networking
8
112 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Characteristics
Distance between repeater and stations Max. 1000 m
Number of repeaters between two stations Max. 1
Number of repeaters per SAFEDLINK network Max. 32
Data rate 'Standard' Max. 315 kbit/s
'Low' data rate Max. 115 kbit/s
The repeater (SAFEDLINK) FN2002
-
A1 is an external component and cannot be
seen in 'SintesoWorks'. Document use in the site documentation.
You will find detailed information on the repeater in the product data 008837.
8.5.3 Interface module DL485/13-xx-ST-SBT
If the FCnet/SAFEDLINK networking is to be managed over large distances, the
system bus can be extended with the interface module DL485/13-xx-ST-SBT and
fiber optic cables.
You will find detailed information about using fiber optic cables and the interface
module DL485/13-xx-ST-SBT in document 008837. See chapter 'Applicable
documents'.
Figure 46: SAFEDLINK system bus extension with interface module DL485/13-xx-ST-SBT via fiber
optic cables
1 System bus FCnet/SAFEDLINK
2 Stations in the FCnet/SAFEDLINK network
3 Interface module DL485/13-xx-ST-SBT
4 Fiber-optic cables for extending the FCnet/SAFEDLINK system bus