Defining operating units and add
12
179 |
Building Technologies
Use Required components Notes
Larger battery capacity for
longer bypass time
● Second carrier (19", power supply)
FHA2022-A1 with 2 power supplies
(150 W)
● Second battery tray (19") FHA2021-A1
Space for card cage (5 slots) or
carrier (19", options) is reduced
Fire controls ● Relay module Z3B171
For installation on a DIN rail, e.g.
on carrier (19", options). Can be
controlled via a programmable I/O.
9 V supply for restricted
degraded mode operation
[FR]
● Battery set 9 V [FR] FCA2010-A1 Supplied without a battery.
Table 56: Components specifically for the FC2080
12.5 Defining operating units and add-ons
The fire control panel FC2080 has no integrated operating unit. Operating unit and
operating add-ons can be integrated as options, but form a ↑ station of their own
within the FC2080. The communication takes place via ↑ FCnet, the supply can be
via the FC2080. The load of the operating unit must be incorporated into the
current balance of the FC2080 in this case.
NOTICE
Product version of the network module is ES
Communication error
● If an optional operating unit is installed in the FC2080,then the operating unit
must be equipped with a ↑ network module (SAFEDLINK) FN2001-A1 and a
See also
2 Defining the operating units [➙ 161]
2 Defining operating add-ons [➙ 162]