9
133 |
Building Technologies
9 Defining controls
Connections for controls are available on the following components / control
panels:
● Fire control panels FC2020, FC2030, FC2040 and FC2060
● Input module
– FDCI221
– FDCI222
● Input/output module
– FDCIO221
– FDCIO222
– FDCIO223
– FDCIO224
– ALS
– FDCAI221 addressable ↑ alarm indicator
● I/O card (↑ remote transmission) FCI2007-A1
● I/O card (programmable) FCI2008-A1
● I/O card (horn/monitored) FCI2009A1
Available control outputs of the hardware components
FC2020/
FC2030
FC2040/
FC2060
FDCI221 FDCI222 FDCIO221 FDCIO223
FDCIO222/
FDCIO224
FCI2008
↑ RT alarm
(relay)
1 1 – – – – – --
Alarm output
(monitored)
1 1 – – – – – --
RT fault (relay) 1 1 – – – – – --
Fault output
(monitored)
1 1 – – – – – --
Monitored horn
lines
1 2 – – 1 2 – --
Monitored
contact inputs
– – 1 4 1 – 4 --
Non-monitored
control
outputs/contact
inputs
8 freely
configura
ble I/Os
12 freely
configura
ble I/Os
– – – – 4 outputs
12 freely
configurab
le I/Os
Table 35: Control outputs
I/O cards for control outputs
● I/O card (↑ remote transmission) FCI2007-A1
● I/O card (programmable) FCI2008-A1
● I/O card (horn/monitored) FCI2009A1