Determining the compact stations
Supply concept
11
146 | 242
Building Technologies
008843_v_en_
--
Fire
Safety
2015
-
-
15
Use Required components Notes
Electrically isolated control
of various functions [NL]
RT interface [NL] FCI2005-N1
Connection of remote
transmission devices with
multiple alarm criteria [CH]
RT interface [CH] FCI2006-C1
Assembled kit with mounting plate,
card E3G091 and connection cable.
Connection with flexible
leads to the options on the
operating unit (instead of
massive conductors)
Connection of shieldings to
earth
Cable set (communication)
FCA2014-A1
Mounted instead of the shield
connection terminal blocks. Can be
used universally for all stations.
2 shield connection terminal blocks,
8 cable clamps on one terminal strip,
and 4 shielded, pre-assembled
cables
Extended networking via
FCnet/LAN or optical
Ethernet
Ethernet switch (modular) FN2012-A1 Replaces FN2008-A1. Also requires:
Connection module (MoNet)
FCA2031-A1
Ethernet module (MM) VN2002-
A1 or Ethernet module (SM)
VN2003-A1
Mounting kit (switch) FHA2029
Connection to external
(public) or company
network
Firewall
Table 41: Additional components for the stations
1
The operating current of the sounder module is a maximum of 2 A (fuse
protection 2 AT), although the maximum output current per sounder is 1 A.
I
total max.
= 2 A = I
Out1
+ I
Out2
+ I
Out3
+ I
Out4
If the sounder module FCA2005 is supplied via the FS20 peripheral module (output
VSYS), the availability of a maximum current of 1 A (1 A fuse) on this output must
be observed. The maximum operating current I
total max
is only 1 A in this case.
See also
2 License keys [ 100]
11.2 Supply concept
The stations are fed with energy in different ways. In this chapter the different
types of energy supply are described in detail.
Use FC20xx FT2040
AC 230 V + batteries Standard Optional
AC 230 V Possible Optional
2 x DC 24 V No Standard
1 x DC 24 V No Possible
Also observe the notes relating to lightning protection in document A6V10225306.