Determining the compact stations
11
146 | 242
Use Required components Notes
Electrically isolated control
of various functions [NL]
● RT interface [NL] FCI2005-N1 –
Connection of remote
transmission devices with
multiple alarm criteria [CH]
● RT interface [CH] FCI2006-C1
Assembled kit with mounting plate,
card E3G091 and connection cable.
Connection with flexible
leads to the options on the
operating unit (instead of
massive conductors)
Connection of shieldings to
earth
● Cable set (communication)
FCA2014-A1
Mounted instead of the shield
connection terminal blocks. Can be
used universally for all stations.
2 shield connection terminal blocks,
8 cable clamps on one terminal strip,
and 4 shielded, pre-assembled
cables
↑ Extended networking via
FCnet/LAN or optical
Ethernet
● Ethernet switch (modular) FN2012-A1 Replaces FN2008-A1. Also requires:
● Connection module (MoNet)
FCA2031-A1
● Ethernet module (MM) VN2002-
A1 or Ethernet module (SM)
VN2003-A1
● Mounting kit (switch) FHA2029
Connection to external
(public) or company
network
● Firewall –
Table 41: Additional components for the stations
1
The operating current of the sounder module is a maximum of 2 A (fuse
protection 2 AT), although the maximum output current per sounder is 1 A.
I
total max.
= 2 A = I
Out1
+ I
Out2
+ I
Out3
+ I
Out4
If the sounder module FCA2005 is supplied via the FS20 peripheral module (output
VSYS), the availability of a maximum current of 1 A (1 A fuse) on this output must
be observed. The maximum operating current I
total max
is only 1 A in this case.
See also
2 License keys [➙ 100]
11.2 Supply concept
The ↑ stations are fed with energy in different ways. In this chapter the different
types of energy supply are described in detail.
Use FC20xx FT2040
AC 230 V + batteries Standard Optional
AC 230 V Possible Optional
2 x DC 24 V No Standard
1 x DC 24 V No Possible
Also observe the notes relating to lightning protection in document A6V10225306.