EasyManua.ls Logo

Siemens FS20 - Connection Factors of the Fdnet Devices

Siemens FS20
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Planning detector lines
Planning an FD
net detector line
7
76 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
7.1.8 Connection factors of the FDnet devices
Determine the following values for each loop and each stub:
Address connection factor AK
Quiescent current connection factor RK
Maximum current connection factor MK
Address connection factor (AK)
The address connection factor defines the number of addresses which are
occupied by a detector line device.
All detector line devices that are directly connected to the detector line have
one address (AK = 1).
The sounder base FDSB291 is not directly connected to the detector line but to
the port for the external alarm indicator. Therefore, it has no address on the
detector line (AK = 0).
External alarm indicators do not have an address on the detector line
(AK = 0) either.
Quiescent current connection factor (RK)
The quiescent current connection factor is a factor for the load of a detector line
device when quiescent.
The quiescent current connection factor does not have any influence on the
detector line calculation. It is only required for the calculation of the power
supply.
Controls inversely actuated by a detector such as locking systems must be
taken into account with a quiescent current connection factor of 1 in quiescent
condition.
Maximum current connection factor (MK)
The maximum current connection factor is a factor for the power load of a
detector line device in case of an alarm. It is used to determine the electric load
of the line card.
Determine the maximum current connection factor (MK) and the quiescent current
connection factor (RK) with the aid of the table below or the outline quantities
tool FX2010.

Table of Contents

Other manuals for Siemens FS20

Related product manuals