EasyManua.ls Logo

Siemens FS20 - Preparing for Recessed Mounting of Compact Stations

Siemens FS20
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Other project planning ste
ps
Preparing for recessed mounting of compact stations
14
231 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
14.2 Preparing for recessed mounting of compact
stations
It is often a good idea to fit a formwork box in the recess for recessed mounting of
compact stations. For fire control panels, a panel thickness of 13 mm is
recommended for the formwork boards (incl. rear board).
The following recess sizes are needed for the formwork box if using a board
thickness of 13 mm (dimensions incl. plasterwork):
Housing Recess width (W) mm Recess height (H) mm Recess depth (D) mm
(incl. rear board)
Installation depth
of housing
Eco 456 424 97.5 84.5
Standard 456 424 177.5 164.5
Comfort 456 822 177.5 164.5
Large extension 456 424 277.5 264.5
Large 456 822 277.5 264.5
Figure 78: Example, formwork box 1 HE
D
2
3
1
H
W

Table of Contents

Other manuals for Siemens FS20

Related product manuals