5.10 Mimic display driver FT2001-A1
The mimic display driver FT2001-A1 is a parallel LED indication for the system-
wide signaling of events and is connected to the FDnet detector line. It has 48
LEDs that are installed on a ground plan panel.
Figure 9: Integration of the mimic display driver into the fire detection installation
1 Mimic display driver
2 Optional external DC or AC supply
Guidelines
External power supply is possible with DC or AC.
Mimic display drivers that are not fed by the detector line (separate power
supply) must be electrically isolated from the system voltage.
Several floor repeater terminals and floor repeater displays, which are
connected to the same line card, must not be operated via an electrically
connected supply.
NOTICE
Influencing the
earth fault monitoring
Faults
Electrical isolation of the supply unit must be present for devices on the FDnet
that are fed separately (with the exception of the transponder).
When an external supply unit is used, it must be taken into account that should
the external supply unit fail, the maximum current connection factor
increases significantly (line failure is possible).
When power supply is ensured via the detector line, the high maximum current
connection factor (MK) must be taken into account.
A maximum of 20 mimic display drivers can be connected per fire control
panel.
FDnet
FT2001
DC/AC