System overview
Extended networking
4
26 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Networking
The two systems are networked with one another in accordance with the rules of
the respective systems FCnet/SAFEDLINK or SIGMANET.
You will find detailed information on Sigmasys networking or D100 P system
networking in the corresponding planning instructions, documents A24205-A334-
A846 and A24205-A337-A970. See chapter 'Applicable documents'.
Module bus cards
Max. two module bus cards:
Detector line cards
I/O cards
Configuration and operation
SOC component
Software from V4.7 onwards; it is no longer necessary
for all SOC components to be replaced with SOP-P.
SIGMANET Person
Machine Interface
Software from V4.8 onwards
SMC base plate Software from V4.8 onwards
SOC P component Software from V9.0 onwards
MAP P component Software from V9.0 onwards
Configuration tool PLAND100 from V9.2 Release 4 onwards
Table 1: Supported SIGMASYS/D100 software versions for connection to FG2020
FG2020 is configured using the PC software FXS2002 (SintesoWorks) with a
PLAN D100 export. SintesoWorks and the FG2020 are connected locally via
Ethernet or via remote access.
According to VDE 0833, the SIGMASYS/D100 P coupling control panel may need
to be equipped with a double CPU, depending on the size of the site.
4.3 Extended networking
An Ethernet switch (modular) FN2012 can be used to consolidate several
networked FS20 fire detection systems to make one composite network
(FCnet/LAN).
This FCnet/LAN is connected via an Ethernet switch (modular) to the individual
FCnet/SAFEDLINK sub-nets in a loop by means of fiber optic cables.
This allows smaller sub-nets to be networked over large distances using a fast
main network. Individual buildings can therefore be connected to a network as sub-
networks, for example.
4.3.1 Extended redundant networking
To retain redundant networking in an extended network in accordance with EN 54,
all network nodes in a sub-net must be connected to the FCnet/LAN via two
Ethernet switches (modular) or stations. Stations are configured as routers and
monitor one another. If the active router station fails, the standby router station
automatically takes over its function.
This type of redundant networking is used for sub-networks with one or more of the
following criteria:
More than 512 FDnet detectors
On a monitored surface of more than 12,000 m
2
If a station takes over system-wide remote transmission