EasyManua.ls Logo

Siemens FS20 - Stations; Fire Control Panels

Siemens FS20
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System overview
Stations
4
28 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
4.4 Stations
4.4.1 Fire control panels
You will find information about the country
-
specific availability of devices in
document 'Delivery Release'.
FC2020 FC2030 FC2040 FC2060 FC2080
Operation
Operating unit Integrated Integrated Integrated Integrated
8
Optional
Operating add-on Max. 1
1
Max. 1 Max. 1 Max. 1 Optional
Detector lines
Number of device addresses
(total)
252 756 504 1512 5000
No. of FDnet addresses
(max.)
252 756 504 1512 5000
Number of integrated FDnet
detector lines:
Without loop extension 2 loops
2
2 loops
2
4 loops
2
4 loops
2
With loop extension 4 loops
2
4 loops
2
8 loops
2
8 loops
2
Card cage (5 slots) Max. 1 Max. 7
Card cage (2 slots) 1 --
Module bus cards
Line card (FDnet/C-NET) Max. 2
3
Max. 5
3
Max. 30
3
Line card (collective) Max. 2
3
Max. 5
3
Max. 30
3
Line card (MS9i) Max. 2
3
Max. 5
3
Max. 30
3
Line card (AnalogPLUS) Max. 2
3
Max. 5
3
Max. 30
3
Line card (interactive) Max. 2
3
Max. 5
3
Max. 30
3
Line card (interactive, Ex) Max. 2
3
Max. 5
3
Max. 30
3
No. of collective stubs (max.) 16 40 240
No. of MS9i devices (max.) 200 500 3000
No. of AnalogPLUS devices
(max.)
756 1512 5000
No. of interactive devices
(max.)
256 640 3840
No. of interactive Ex devices
(max.)
64 160 960
I/O card (programmable) Max. 1 Max. 5
3
Max. 37
3
I/O card (horn-monitored) Max. 1 Max. 1 Max. 7
3
I/O card (RT) Max. 1 Max. 1 Max. 7
3

Table of Contents