Building Technologies
FC2020 FC2030 FC2040 FC2060 FC2080
Supply
Power supply 70/150 W
1
150 W 150 W 150 W
Max. 2 kits of
3x 150 W
Battery pair (depending on the
housing)
Max. 26 Ah Max. 26 Ah Max. 26 Ah Max. 45 Ah
Max. 2 kits of
100 Ah
Supply input 3 [FR] 1 1 1 1 1
External DC supply (24 V) ― ― ― ― ―
Inputs and outputs
↑ RT alarm, relay 1 1 1 1 ―
7
RT fault, relay 1 1 1 1 ―
7
RT alarm monitored 1 1 1 1 ―
7
RT fault monitored 1 1 1 1 ―
7
Horn output, monitored 1 1 2 2 ―
7
Freely configurable
inputs/outputs
8 8 12 12 ―
7
Options
Loop extension (FDnet) Max. 1 Max. 1 Max. 2 Max. 2 ―
↑ Network module
(SAFEDLINK)
Max. 2 Max. 2 Max. 2 Max. 2 Max. 2 integrated
Ethernet switch (modular)
10
Max. 1 Max. 1 Max. 1 Max. 1 Max. 1
RS232 module Max. 2 Max. 2 Max. 2 Max. 2 Integrated
RS485 module Max. 2 Max. 2 Max. 2 Max. 2 Integrated
Fire brigade periphery module
[DE]
Max. 1 Max. 1 Max. 1 Max. 1 ―
6
Event printer (built-in) Max. 1 Max. 1 Max. 1 Max. 1 ―
5
LED indicator (internal); 24
yellow and 24 red LEDs each
Max. 5 Max. 5 Max. 5 Max. 5 ―
5
FBA terminal [CH] Max. 1 Max. 1 Max. 1 Max. 1 ―
5
EVAC-NL operating unit [NL] Max. 1 Max. 1 Max. 1 Max. 1 ―
5
Sounder module Max. 2 Max. 2 Max. 2 Max. 2 ―
RT interface [NL] Max. 1 Max. 1 Max. 1 Max. 1 ―
RT interface [CH] Max. 1 Max. 1 Max. 1 Max. 1 ―
↑ License key Max. 1 Max. 1 Max. 1 Max. 1 Max. 1, >S2 only
Key switch (Kaba) Max. 1 Max. 1 Max. 1 Max. 1 ―
5
Key switch (nordic) Max. 1 Max. 1 Max. 1 Max. 1 ―
5
Door contact kit [DE] Max. 1 Max. 1 Max. 1 Max. 1 ―
Table 2: Overview of the stations and installable options
1
Depending on housing size
2
It is also possible to connect two ↑ stubs instead of one loop.
3
Mixed variants possible
4
Max. one repeater between two stations