Project planning of indication and operation d
evices
LED module FTO2008
-
A1
5
43 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
5.6 LED module FTO2008-A1
(1) LED red/green
(2) LED yellow
(3) Inscribable fields
The LED module FTO2008-A1 contains 24 indicator zones. Each zone
contains one red / green bicolor LED and one yellow LED.
Any events can be assigned to the LEDs. Each LED may be configured as a
static or flashing indicator. Normally the LED indicator is used as a zone
indicator.
The LED module is connected to the station-internal bus and can be cascaded
to up to a maximum of five LED modules.
The LED module is not individually available as an option. It is permanently
integrated in the following components:
Operating unit (+LED indicator) FCM2037-A2
Operating add-on (2x LED indicators) FCM2038-A2
Operating add-on (4x LED indicators) FCM2036-A2
The operating units and operating add-ons are permanently integrated
depending on the station type. The number of indicator zones required
determines which station must be ordered.
5.7 FBA terminal FTO2004-C1 [CH]
Standardized fire brigade operating and indicator panel according to Swiss
standards. The FBA terminal is pre-installed in the corresponding operating unit.
The FBA terminal is connected to the station-internal bus.
The FBA terminal is not individually available as an option. It may be permanently
built-in, depending on the station type.
5.8 Floor repeater terminal FT2010 and floor repeater
display FT2011
Floor repeater terminal FT2010 Floor repeater display FT2011