4
30 | 242
5
With the FC2080, only optional as a separate station
6
Functionality via I/O card (programmable) FCI2008-A1 and/or FDCIO224 and key
safe adapter
7
Only via I/O card (RT) and I/O card (horn/monitored), mixed variants possible
8
Fire control panels FC2060 with the PMI & mainboard FCM2004 are not
supported by market package MP-EN 4.0 because of memory restrictions.
9
FC2080 must not be used as a router.
10
Only installed for stations in Comfort and Large housings and the FC2080. Other
stations in separate empty housings.
4.4.2 Fire terminals
You will find information about the country
specific availability of devices in
document 'Delivery Release'.
FT2040 FT2080
Operating unit Integrated
Comfort operating
unit
↑ Detector lines ― ―
Module bus cards ― ―
Inputs and outputs ― ―
Supply
Power supply Optional (70 W)
Optionally with power
supply (70 W) in sep.
housing on fire
terminal board
Batteries (depending on the housing) Optional (7 Ah)
Supply input 3 [FR] 1
External DC supply (24 V) Possible
Options
↑ Loop extension (FDnet)
1
― ―
↑ Network module (SAFEDLINK) Max. 2 Max. 2
Ethernet switch (modular) Sep. housing Sep. housing
RS232 module Max. 2 Max. 2
RS485 module Max. 2 Max. 2
Fire brigade periphery module [DE] ― ―
Event printer (built-in) Max. 1 ―
Front indicator (Touch) ― Integrated
LED indicator (internal); 24 yellow
and 24 red LEDs each
Max. 5 ―
FBA terminal [CH] Max. 1 Max. 1
EVAC-NL [NL] Max. 1 ―
Sounder module ― ―
RT interface [NL] ― ―
RT interface [CH] ― ―