System limits
Determining the outline quantities of the software
10
140 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
10 System limits
10.1 Determining the outline quantities of the software
The number of logic units and controls is limited for each fire control panel. The
following limit values apply for the different fire control panels:
General restriction
A maximum of 1000 'Zones' are permitted for each 'Area'.
Parameters FC2020 FC2030 FC2040 FC2060
4
FC2080
'Areas' 4 4 4 8 24
'Sections' 50 200 100 200 400
'Zones' per 'Station' 252 756
1
504 1512 3000
'Zones' per 'Area' 1000 1000 1000 1000 1000
Fire incident control groups
2
50 150 100 150 250
EVAC control groups
2
50 150 100 150 250
Controls per control
group
2
100 100 100 100 100
Total of all control groups
and controls per 'Station'
2
100 200 200 350 500
Causes per control 50 50 50 50 50
Effects per control 50 50 50 50 50
Effects per 'Station'
3
700 1400 1400 2100 3000
Entries in event memory
5
2000 2000 2000 2000 2000
Table 39: Maximum number of logic units/controls for each fire control panel
1
The FC2030 fire control panel is based on the FC2020 and can also hold a
maximum of 2 line cards for detector line migration.
2
Controls are grouped in control groups, for simplified configuration and operation
in the system. Control groups need system resources; the number of control
groups (e.g., fire control groups and EVAC control groups) must therefore be taken
into account when determining the outline quantities.
3
The effect must be on the same station as the configured control.
4
Fire control panels FC2060 with the PMI & mainboard FCM2004 are not
supported by market package MPEN 4.0 because of memory restrictions.
5
May be higher for specific countries (number of events, standard 2000 + number
of guaranteed alarms + number of guaranteed isolations).