Monitored outputs (I/O card (remote transmission) FCI2007
-
A1 and I/O card (horn/monitored) FCI2009
-
A1)
9
139 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Planning steps
1. Determine the load resistance that will be connected at the output (Rload),
e.g. sounder DS10: Rload = 24 V/0.42 A = 57.2 ohm
2. Define the minimum required voltage of the sounder (Uload), e.g. datasheet
DS10: U = 19…29 V -> Uload = 19 V
3. In the dimensioning table, find the row that corresponds to these values and
determine the associated values.
The monitored resistance value must be within the range for the monitoring
resistance, otherwise a fault message will be displayed at the station. You will
find detailed information about this in document Product data 008837.
Dimensioning of load for monitored fault output
Use the dimensioning table to determine the following:
RcableMax
Example from dimensioning table 1
For Rload >40 ohm
RcableMax = 6 ohm
For the Rx and diode, make sure the dimensioning is correct (maximum power
dissipation, maximum diode reverse voltage >30 V, etc.).
Dimensioning table for monitored fault output
Load Monitoring
RIoad [Ω] UIoad [V] RcableMax. [Ω]
>150 <21 1.6
<15 62
>1000 <21 10
<15 200
>2000 <21 21
<15 200
>4000 <21 43
<15 200
Table 38: Dimensioning table for monitored fault output
RIoad Load resistance [Ω]
UIoad Load voltage (Minimum) [V]
RcableMa
x.
Maximum permitted cable resistance [Ω]