Planning the networking of the stations
Special features of SAFEDLINK networking with FC2080
8
113 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Characteristics
Length of the fibre optic cable:
Multi-mode
Single mode
Max. 2000 m
Max. 15000 m
Connection length to station Max. 100 m
Required converter between two stations 2
Optical connection ST
Number of fibers between two interface modules 2
Data rate 'Standard' Max. 315 kbit/s
'Low' data rate Max. 115 kbit/s
8.6 Special features of SAFEDLINK networking with
FC2080
The FCnet networking of the fire control panel FC2080 differs in the following
respects from that of the compact control panels:
Internal connection to optional operating unit
Network module (SAFEDLINK) as well as wiring and installation location
All other points, such as characteristic data and devices that can be connected on
FCnet, correspond to SAFEDLINK networking.
Example of standalone fire control panel FC2080 with operating unit
The fire control panel FC2080 is operated without an operating unit. The optional
operating unit for the FC2080 is autonomous to the FC2080 and corresponds to a
separate station. Communication is via the FCnet as shown.
1. Processor unit (19", FC2080) with
CPU card (FC2080) and
communication card (FC2080)
2. Operating unit (operating unit and
operating add-ons)
3. FCnet networking of the FC2080
with the optional operating unit
1
3
2