EasyManua.ls Logo

Siemens FS20 - Sequence

Siemens FS20
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Planning detector lines
Planning an FDnet detector line
7
60 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Limited planning with the aid of these instructions
Limited planning of the detector lines using these instructions allows a detector line
to be verified. The following restrictions must be taken into account:
Maximum numbers of devices:
1 loop, maximum 252
2 loops, maximum 126 in each case
4 loops, maximum 64 in each case
8 stubs, maximum 32 in each case
The same topologies must be connected on all line cards (only loops or only
stubs).
Each loop or stub must be verified separately.
If one of the aforementioned restrictions cannot be adhered to, the outline
quantities tool must be used for planning the detector lines.
7.1.1 Sequence
Procedure per loop/ stub
1. Determine the type and location of the detector line devices.
2. Define the topology of the detector line.
3. Define the assignment of the lines to the line cards.
4. Define the cable type.
5. Define the cable length and calculate the cable resistance and cable
capacitance.
6. Determine the connection factors for the detector line devices.
7. Check the load of the line card using the outline quantities tool or the
diagrams. The maximum current connection factor must be lower than the
reserve of the maximum current connection factor.
See also
2 Line topology [ 68]
2 Cabling line devices [ 70]
2 Cable length [ 71]
2 Connection factors of the FDnet devices [ 76]
2 Maximum current connection factor reserve [ 79]

Table of Contents

Other manuals for Siemens FS20

Related product manuals