Planning the networking of the stations
Access components/function and access type
8
103 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
8.3.2 Access to the SAFEDLINK station
Figure 40: Example of SAFEDLINK stations
If a
SAFEDLINK
Station
is configured as
'
GAP
' or '
Secondary GAP
', it must
also be configured as a router or a standby router; otherwise, local or general
access via the Ethernet port will not be possible.
Local access
Item no. Designation/function Ethernet address
SAFEDLINK
address
Notes
1
Ethernet interface to
SAFEDLINK station
192.168.200.1
IP address of Ethernet interface. A
DHCP server runs on the Ethernet
interface of each SAFEDLINK
station to assign the address
192.168.200.5 to the connected PC
2 SAFEDLINK stations 192.168.1.x
IP address range for SAFEDLINK
network
3 SAFEDLINK network
4 Ethernet connection
5
Uploading,
downloading
Initializing the
station
Updating the
firmware
SintesoView
192.168.200.5
Ethernet client is configured to
automatically reference an IP
address (see item 1)
Table 26: Local access
1
2
2
3
4
5
2