Planning the networking of the stations
Access components/function and access type
8
104 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Access via GAP station
Item no. Designation/function Ethernet address
SAFEDLINK
address
Notes
1 GAP station 192.168.201.1
Configured as GAP with DHCP
server function.
Router station 192.168.100.3
Configured as router station
(192.168.100.3 is an example of an
Ethernet address)
2 SAFEDLINK stations 192.168.1.x
Standard address range for
SAFEDLINK stations is 192.168.1.x
(can be changed)
3 SAFEDLINK network
4 Ethernet connection
5
Uploading,
downloading
SintesoView
Management
station
192.168.201.5
Ethernet client is configured to
automatically reference an IP
address (see item 1)
Table 27: Access via GAP station
Access via address
Item no. Designation/function Ethernet address
SAFEDLINK
address
Notes
1 GAP station
Configured as GAP without DHCP
server function
Router station 192.168.100.3
Configured as router station
(192.168.100.3 is an example of an
Ethernet address)
2 SAFEDLINK stations 192.168.1.x
Standard address range for
SAFEDLINK stations is 192.168.1.x
(can be changed)
3 SAFEDLINK network
4 Ethernet connection
5
Uploading,
downloading
SintesoView
Management station
192.168.100.100
IP address manually configured in
the same address range as IP
address for GAP station
Table 28: Access via address