Planning the networking of the stations
Guidelines
8
130 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Parameters FCnet/SAFEDLINK FCnet/Ethernet (sub-net)
Maximum number of repeaters between two
stations
1
Max. number of repeaters 32
Max. length of line between interface module and
stations
100 m
Maximum number of interface modules between
two stations
1 pair
Max. number of interface modules 32 pairs
Max. length of line of all electrical connections
(copper cables) in the optical network
1000 m
Maximum number of fiber optic cable network
modules between two stations
1
Maximum number of fiber optic cable network
modules
32
Table 32: Parameters of the SAFEDLINK networking types
1
Even when using an external LWL network module (SM/MM), the maximum
length of the electric FCnet between the stations must not be longer than 1000 m.
8.16.3 Guidelines for extended networking
Please observe the following guidelines for extended networking via FCnet/LAN
with an Ethernet switch:
Ethernet switch (MM) FN2008-A1 may be used in stations MP3.
Ethernet switch (modular) FN2012-A1 may only be used in stations MP6.
Mixed operation with both Ethernet switches is not permitted.
Sub-nets with more than 512 fire detectors must be coupled to the FCnet/LAN
redundantly using two Ethernet switches (EN 54).
Sub-nets with superordinate functions (remote transmissions, alarming
devices, master operation) must be coupled to the FCnet/LAN redundantly
using two Ethernet switches (various country-specific 'Codes of Practice').
Sub-nets monitoring areas larger than 12000 m
2
must be coupled to the
FCnet/LAN redundantly using two Ethernet switches (VDE 0833-2).
Redundant lines should be routed on separate sections to rule out the
possibility of damage by the same event.
The following table shows the most important parameters.
Parameters FCnet/LAN
Max. length of line between the stations 3000 m
Max. number of stations in entire network (all sub-networks) 64
Max. number of stations per SAFEDLINK sub-net 16
Max. number of SAFEDLINK sub-networks 14
Max. number of Ethernet sub-networks per SAFEDLINK sub-network Not admissible
FCnet/LAN cabling:
Multimode fiber optic cable (ST connection)
50/125 µm
62.5/125 µm
Table 33: Networking parameters