Determining the compact stations
Determining additional compact station components
11
145 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Use Required components Notes
Connection of an ESPA-
4.4.4 interface
RS485 module (isolated) FCA2002-A1
(integrated in FC2080)
For forwarding information to
systems for pagers, light signals, and
telecommunications.
The ESPA-4.4.4 interface is a
product from a third party.
Alarming via telephone or
pager
ESPA-4.4.4 interface
RS485 module (isolated) FCA2002
(integrated in FC2080)
An RS485 module is required for the
ESPA-4.4.4 interface.
The ESPA-4.4.4 interface is an IFAM
product.
Fire control Relay module Z3B171
For mounting on a DIN rail. Can be
controlled by a central internal I/O or
an input/output module FDCIO222 or
FDCIO224.
Standard extinguishing
interface
Input/output module FDCIO224
Is connected to FDnet to activate an
extinguishing control unit.
Networking via FCnet Network module (SAFEDLINK)
FN2001-A1
In accordance with the requirements
in degraded mode, two network
modules (SAFEDLINK) can be
integrated.
FCnet networking over
larger distances
Repeater (SAFEDLINK) FN2002-A1
For FCnet extension, max. 1
repeater between 2 stations; requires
a supply of DC 9...30 V.
Interface module DL485/13-xx-ST-SBT
For FCnet extension, max. 1
segment between 2 stations;
requires a supply of DC 9...30 V per
module.
Fiber optic cable network module (SM)
FN2006-A1
Fiber optic cable network module (MM)
FN2007-A1
For optical FCnet over long
distances. When installed in the
station housing, the available
mouting space must be taken into
consideration.
In all FS20 stations, the fiber optic
cable network module can only be
mounted horizontally. (See
document Mounting/Installation
008851)
Release operation with key Key switch (Kaba) FTO2005-C1
Key switch (nordic) FTO2006-B1
9 V supply for restricted
degraded mode operation
[FR]
Battery kit 9 V [FR] FCA2010-A1 Supplied without a battery.
Connecting additional
horns
Sounder module FCA2005-A1
Divides a sounder output into 4
outputs. A maximum of 2 modules
can be interconnected. Observe
operating current
1
.
Input/output module FDCIO223
Connection of two monitored
sounders
I/O card (horn/monitored) FCI2009A1
The I/O card is used in the card cage
and can only be used in the fire
control panels FC2030 and FC2060.