Determining the compact stations
Determining additional compact station components
11
144 | 242
Building Technologies
008843_v_en_
--
Fire
Safety
2015
-
-
15
Use Required components Notes
Additionally monitored
horn lines or inputs/outputs
I/O card (horn/monitored) FCI2009A1
This I/O card has 8 monitored horn
outputs and is used in the card cage
of the fire control panels FC2030 and
FC2060.
I/O card (RT) FCI2007-A1
This I/O card can be configured for
two monitored horn outputs or two
programmable inputs/outputs. It is
used in the card cage of the fire
control panels FC2030 and FC2060.
LED indicator for events LED indicator (internal) FTO2002-A1
LED module FTO2008-A1
Installed in the operating unit and
operating add-ons. Actuation via
configurable I/Os.
Logging system-wide
events
Internal event printer FTO2001-A1
External printer Fujitsu DL3750+
Print server PS01a from SEH
RS232 module (isolated) FCA2001-A1
(must be ordered separately)
The internal event printer can be
installed in various ways depending
on the station and version. This
can restrict the dimensions of the
batteries.
The printers are connected via the
RS232 module.
Only 1 printer can be connected for
each RS232 module.
The external printer FUJITSU
DL3759+ can also be operated on
the Ethernet via the print server
PS01a from SEH.
Connecting SintesoView
and/or BACnet third-
party products (monitoring
only)
License key (S1) FCA2033-A1
Installation on the back of the
operating unit.
BACnet extension for third-
party products (supervision
and basic control)
License key (S2) FCA2034-A1
Installation on the back of the
operating unit.
BACnet extension for third-
party products (full control)
and Sinteso Mobile
License key (S3) FCA2035-A1
Installation on the back of the
operating unit.
Connecting peripheral
devices in compliance with
VdS [DE] (e.g., local
alarm)
Fire brigade periphery module
FCI2001-D1 [DE]
A mounting plate FHA2007 is also
necessary for this module in the
standard housing.
In the Comfort housing this module
can be mounted next to the
periphery board.
Class 3 key depot [DE] Fire brigade periphery module
FCI2001-D1 [DE]
Door contact kit FCA2009-A1 [DE]
Depending on the housing and
options used, an FHA2007 mounting
plate may be needed for mounting of
the fire brigade periphery module
FCI2001-D1.
Connection of a FAT [DE] RS485 module (isolated) FCA2002-A1
(integrated in FC2080)
Fire brigade indication panel in
accordance with DIN 14662
Connection of a serial FBF
[DE]
RS485 module (isolated) FCA2002-A1
(integrated in FC2080)
Fire brigade operating panel in
accordance with DIN 14661

Table of Contents