Determining the compact stations
Determining additional compact station components
11
144 | 242
Use Required components Notes
Additionally monitored
horn lines or inputs/outputs
● I/O card (horn/monitored) FCI2009A1
This I/O card has 8 monitored horn
outputs and is used in the card cage
of the fire control panels FC2030 and
FC2060.
● I/O card (RT) FCI2007-A1
This I/O card can be configured for
two monitored horn outputs or two
programmable inputs/outputs. It is
used in the card cage of the fire
control panels FC2030 and FC2060.
LED indicator for events ● LED indicator (internal) FTO2002-A1
● LED module FTO2008-A1
Installed in the operating unit and
operating add-ons. Actuation via
configurable I/Os.
Logging system-wide
events
● Internal event printer FTO2001-A1
● External printer Fujitsu DL3750+
● Print server PS01a from SEH
● RS232 module (isolated) FCA2001-A1
(must be ordered separately)
The internal event printer can be
installed in various ways depending
on the ↑ station and version. This
can restrict the dimensions of the
batteries.
The printers are connected via the
RS232 module.
Only 1 printer can be connected for
each RS232 module.
The external printer FUJITSU
DL3759+ can also be operated on
the Ethernet via the print server
PS01a from SEH.
Connecting SintesoView
and/or ↑ BACnet third-
party products (monitoring
only)
● ↑ License key (S1) FCA2033-A1
Installation on the back of the
operating unit.
BACnet extension for third-
party products (supervision
and basic control)
● License key (S2) FCA2034-A1
Installation on the back of the
operating unit.
BACnet extension for third-
party products (full control)
and Sinteso Mobile
● License key (S3) FCA2035-A1
Installation on the back of the
operating unit.
Connecting peripheral
devices in compliance with
↑ VdS [DE] (e.g., local
alarm)
● Fire brigade periphery module
FCI2001-D1 [DE]
A mounting plate FHA2007 is also
necessary for this module in the
standard housing.
In the Comfort housing this module
can be mounted next to the
periphery board.
Class 3 key depot [DE] ● Fire brigade periphery module
FCI2001-D1 [DE]
● Door contact kit FCA2009-A1 [DE]
Depending on the housing and
options used, an FHA2007 mounting
plate may be needed for mounting of
the fire brigade periphery module
FCI2001-D1.
Connection of a FAT [DE] ● RS485 module (isolated) FCA2002-A1
(integrated in FC2080)
Fire brigade indication panel in
accordance with DIN 14662
Connection of a serial FBF
[DE]
● RS485 module (isolated) FCA2002-A1
(integrated in FC2080)
Fire brigade operating panel in
accordance with DIN 14661