Defining controls
Guidelines
9
134 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
FCI2008 FCI2009 FCI2007
RT alarm (relay) -- -- 1
Alarm output (monitored) -- (8)
1
(2)
1
RT fault (relay) -- -- 1
Fault output (monitored) -- -- 1
Monitored horn lines -- 8 2
Monitored contact inputs -- -- --
Non-monitored control
outputs/contact inputs
12 freely configurable I/Os -- 2 freely configurable I/Os
Table 36: Control outputs of the I/O cards
1
Can be configured as horn or alarm output
Notes
The outputs can be used for any controls. Any events, commands and signal
inputs can be put in an OR, AND and NOT relation.
Controls can be configured system-wide. This means that the causes can
come from any point in the system.
The control must always be configured in that control panel where the control
output is located.
The controls can be configured as activated or deactivated with a delay in a
range of 0…30 minutes.
The onboard inputs/outputs in the fire control panels may be configured as
inputs or outputs.
If an onboard input/output is configured as an input in the fire control panel, it is
activated by applying 0 V.
If an onboard input/output is configured as an output in the fire control panel, it
switches 0 V when active (open drain).
Example: Onboard input/output circuitry
Figure 58: Example: Plug X8 on periphery board (2 loops)
1 Configured as output
2 Configured as input