9
134 | 242
FCI2008 FCI2009 FCI2007
↑ RT alarm (relay) -- -- 1
Alarm output (monitored) -- (8)
1
(2)
1
RT fault (relay) -- -- 1
Fault output (monitored) -- -- 1
Monitored horn lines -- 8 2
Monitored contact inputs -- -- --
Non-monitored control
outputs/contact inputs
12 freely configurable I/Os -- 2 freely configurable I/Os
Table 36: Control outputs of the I/O cards
1
Can be configured as horn or alarm output
Notes
● The outputs can be used for any controls. Any events, commands and signal
inputs can be put in an OR, AND and NOT relation.
● Controls can be configured system-wide. This means that the causes can
come from any point in the system.
● The control must always be configured in that control panel where the control
output is located.
● The controls can be configured as activated or deactivated with a delay in a
range of 0…30 minutes.
● The onboard inputs/outputs in the fire control panels may be configured as
inputs or outputs.
● If an onboard input/output is configured as an input in the fire control panel, it is
activated by applying 0 V.
● If an onboard input/output is configured as an output in the fire control panel, it
switches 0 V when active (open drain).
Example: Onboard input/output circuitry
Figure 58: Example: Plug X8 on periphery board (2 loops)
1 Configured as output
2 Configured as input