Determining the components of the FC2080
12
178 | 242
Use Required components Notes
Connecting additional
horns
● I/O card (horn/monitored) FCI2009A1
This I/O card provides 8 horn
outputs.
● Only 1 I/O card
(horn/monitored) per card cage
(5 slots)
● Input/output module FDCIO223
Connection of two monitored
sounders.
● Sounder module FCA2005-A1
Divides a sounder output into 4
outputs. A maximum of 2 modules
can be interconnected. Observe
the operating current.
Programmable
inputs/outputs
● I/O card (programmable) FCI2008-A1
FDnet lines ● ↑ Line card (FDnet/C-NET) FCL2001-A1
252 addresses and 4 ↑ loops per
card
Connecting collective
detectors
● Line card (collective) FCL2002-A1 8 ↑ stubs of 32 devices per card
Connecting MS9i detectors ● Line card (MS9i) FCL2003-A1 2 loops of 50 devices or
2 stubs of 32 devices
Connecting AnalogPLUS
detectors
● Line card (AnalogPLUS) FCL2005-A1 4 loops of 128 devices or
4 stubs of 32 devices
Connecting interactive
detectors
● Line card (interactive) FCL2006-A1 1 loop with 128 devices or
1 stub with 32 devices
Connecting interactive Ex
detectors
● Line card (interactive Ex) FCL2007-A1
1 stub with 32 devices via Ex
separator
Installation of additional
devices on DIN rail
● Carrier (19", options) with 2 DIN rails,
one on top of other
● Carrier (19", card cage) with DIN rails
● Separate DIN rail at the right-hand side
wall
Class 3 key depot [DE] ● Key safe adapter SDA3000
FSD must be connected via key
safe adapter in the case of the
FC2080.
Requires I/O module or I/O card
(programmable) FCI2008.
Power supply
● Carrier (19", power supply) FHA2022-A1
with 2 power supplies (150 W)
● Battery tray (19") FHA2021-A1
Basic components
Large current range
● Third power supply (150 W, B) FP2005-
A1
Is installed on carrier (19", power
supply)
● Second carrier (19", power supply)
FHA2022-A1 with 2 power supplies
(150 W)
● Third or sixth power supply (150 W, B)
FP2005-A1
Requires second battery tray (19")
FHA2021-A1