Planning the networking of the stations
Remote access to
the extended network with GAP
8
125 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Item no. Designation/function
Ethernet
address(es)
SAFEDLINK
address
Notes
1 'GAP' station and
Router station
192.168.201.1
192.168.100.1
Configured as GAP with DHCP
server function and router function
2 SAFEDLINK stations
3 Router station
4 Standby router stations
5
Ethernet station and
'Secondary GAP'
6 SAFEDLINK sub-net 1 192.168.1.x
IP address range for SAFEDLINK
sub-net 1 (pre-setting, can be
changed)
7 FCnet/LAN 192.168.100.x
IP address range for Ethernet sub-
net (pre-setting, can be changed)
8 SAFEDLINK sub-net 2 192.168.2.x
IP address range for SAFEDLINK
sub-net 2 (pre-setting, can be
changed)
9
Ethernet switch
(modular) FN2012
Any
Address must not be the same as
the address in the FCnet/LAN
10 Ethernet connection
Connected to Ethernet switch
(modular) of the standby station
(example)
11 Management station 10.169.29.82
Ethernet participants from external
sub-net (sample address),
connected to firewall
12 Firewall 192.168.100.2
10.169.29.80
Sample addresses
13
Management station via
'Secondary GAP'
10.169.30.01 Sample address
Table 31: External access to extended network via GAP