Planning the networking of the stations
SAFEDLINK networking
8
109 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Characteristics
Stations that can be networked via
FCnet/SAFEDLINK, without BACnet configuration
(e.g., management station)
Max. 32
Stations that can be networked via
FCnet/SAFEDLINK, with BACnet configuration
(e.g. management station)
Max. 16
Distance between the stations Max. 1000 m
Data rate 'Standard' Max. 315 kbit/s
'Low' data rate Max. 115 kbit/s