Defining controls
Monitored outputs (I/O card (remote transmission) FCI2007
-
A1 and I/O card (horn/monitored) FCI2009
-
A1)
9
136 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Dimensioning of load decoupled with diode (EN 54)
Use the dimensioning table to determine the following:
RcableMax
The range for the Reol along with its power
Example from dimensioning table 1
For Rload >50 ohm
RcableMax = 1.5 ohm
Reol = 50…60 ohm
Peol = 14.8 W
To reduce the required power dissipation of Reol to 0.25 W, Reol can be
decoupled with an additional diode D2.
Make sure the dimensioning is correct:
For the reverse voltage and power dissipation in the case of diode D2. The
Schottky diode 1N5819 is recommended (maximum diode reverse voltage
>30 V). The maximum permissible resistance Reol is 3000 ohm with diode D2.
The absolute measurement accuracy is influenced. This has no effect on the
monitoring accuracy.
For the power dissipation and forward current in the case of load decoupling
diode D1. Recommended depending on the power range: e.g., MBR760 for
Rload <1000 ohm and, e.g., 1N4448 for Rload >=1000 ohm
Dimensioning table for monitored alarm and horn outputs with
decoupled load (EN 54)
Load Monitoring
RIoad [Ω] UIoad [V] RcableMax. [Ω] Reol Min [Ω] Reol Max [Ω] Peol [W]
>20 <21 1 60 100 12.3
<15 6 100 240 7.4
<10 14.3 200 570 3.7
>50 <21 1.5 50 60 14.8
<15 4.6 50 185 14.8
<10 10.1 50 405 14.8
>100 <21 3 100 119 7.4
<15 9 100 370 7.4
<10 20 100 810 7.4
>1000 <21 30 1000 1190 0.74
<15 92 1000 3700 0.74
<10 200 1000 5500 0.74
>2000 <21 59 2000 2378 0.37
<15 185 2000 5500 0.37
<10 200 2000 5500 0.37
>4000 <21 118 4000 5500 0.18
<15 200 4000 5500 0.18
<10 200 4000 5500 0.18