Determining the compact stations
Determining the batteries and power supply
11
152 | 242
Consumer Type I
R
[mA] I
A
[mA] Qty. I
R total
I
A total
Notes
Line card (interactive) FCL2006-A1 63 63 For FC2030, FC2060
Line card (interactive Ex) FCL2007-A1 63 63 For FC2030, FC2060
I/O card (programmable) FCI2008-A1 40 40 For FC2030, FC2060
I/O card (horn/monitored) FCI2009-A1 55 55 For FC2030, FC2060
IO card (remote
transmission)
FCI2007-A1 70 70 For FC2030, FC2060
LED indicator (internal) FTO2002-A1 4 70 Per LED module
LED module FTO2008-A1 4 70
EVAC-NL operating unit
[NL]
FTO2007-N1 6 30 10-zone EVAC
Operating add-on
(2xEVAC term.) [NL]
FCM2008-
N1
12 60
Operating add-on for 20-
zone EVAC
FBA terminal [CH] FTO2004-C1 4 50
↑ Network module
(SAFEDLINK)
FN2001-A1 40 40
Sounder module FCA2005-A1 20
Max.
1 A
Depending on the
number of connected
horns
RT interface [NL] FCI2005-N1 0 240 mA All relays activated
RT interface [CH] FCI2006-C1 0 100 mA All relays activated
Ethernet connection 15 15
With networking and
connection of external
printer via the Ethernet
RS232 module (isolated) FCA2001-A1 11 11 I
R
= no-load operation
I
A
= send/receive
RS485 module (isolated) FCA2002-A1 11 11
Event printer (built-in) FTO2001-A1 50…100
Min. 50 mA, depending
on frequency of printing
Ethernet switch (modular) FN2012-A1
Min. 95 / max.
190 mA
Standby / maximum for
supply via MoNet
Firewall Depending on type
Ethernet switch (MM) FN2008-A1 Max. 215 mA
Security module (firewall) FN2009-A1 Max. 250 mA
Fire brigade periphery
Fire brigade periphery
module [DE]
FCI2001-D1 58 62
Consumers on the fire
brigade periphery module
External consumers
Detector lines (FDnet)
1
0.6 x ƩRK
0.6 x
ƩMK
Detector lines (collective) FCL2002-A1 19/stub
30/stub
for
alarm
↑ Stub on line card
(collective)