Other project planning steps
Wiring instructions
14
234 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Guidelines
A separate circuit with a separate fuse must be available for the mains supply
line.
The mains fuse rating must be 10 A.
The mains fuse for the fire control panel must be marked explicitly.
The line cross-section of the mains supply line must be 3 x 1.5 mm
2
at
minimum (NYM-J cable).
All supply lines must be realized from above or behind.
The mains cable must be wired to the mains separator terminals from above on
the left of the housing.
The mains supply lines must not be laid inside the EMC
-
critical zone.
If the batteries are built in a separate housing, the mains line may be fed from
below.
Separate housings for the batteries must be mounted in the immediate vicinity
of the station.