System overview
FS20 Fire Detection System Setup
4
33 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
1 Fire terminal FT2040 as standard operating terminal
2 Fire control panel FC2020 with an integrated FDnet line card
3 Fire control panel FC2040 with two integrated FDnet line cards
4
Fire control panel FC2030 with an integrated FDnet line card and card cage for two additional FDnet line
cards, line cards for detector migration (collective, MS9i, interactive, AnalogPLUS), or I/O cards.
5
Fire control panel FC2030 with two integrated line cards (FDnet/C-NET) and card cage for five additional
line cards (FDnet/C-NET), line cards for detector migration (collective, MS9i, interactive, AnalogPLUS), or
I/O cards
6
Fire control panel FC2080 in 19" cabinet with line cards (FDnet/C-NET), line cards for detector migration
(collective, MS9i, interactive, AnalogPLUS) as well as I/O cards, optional operating unit, and optional
operating add-ons
7 Addressable FDnet detector lines
8
Addressable FDnet detector lines via installable line cards (FDnet/C-NET), optional with the FC2030,
FC2060, and FC2080
9
Additional installable line cards for detector migration (collective, MS9i, interactive, AnalogPLUS) with the
FC2030, FC2060, and FC2080
10 Additional inputs and outputs via installable I/O cards with the FC2030, FC2060 and FC2080
11
System-wide remote transmission, can be executed from a fire control panel (with I/O card in the case of
the FC2080)
12 Alarm sounder on the FDnet detector line
13
Floor repeater terminal FT2010 for the system-wide display and operation of the most important
information and functions via the FDnet detector line
14
Input/output module FDCIO222 for the connection of an extinguishing control unit XC10 via the FDnet
detector line
15
Input/output module (transponder) for the connection of collective detector lines or universal I/Os via
the FDnet detector line
16
Floor repeater display FT2011 for the system-wide display of the most important information via the
FDnet detector line
17 Mimic display driver FT2001 for the system-wide optical signaling of events via the FDnet detector line
18 License key, for SintesoView or BACnet
19 Connection of a management station via BACnet/Ethernet
20 PC-based operating unit for system-wide operation (SintesoView)
21 PC-based configuration tool SintesoWorks for the configuration of the entire system