Planning detector lines
Planning an FDnet detector line
7
67 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Line card (FDnet/C-NET) for card cage
Figure 20: Line distribution on line card (FDnet/C-NET)
1 Integrated line card 1
2 Integrated line card 2
Lx / Lxa Loop or partial loop
FDnet loop
Loop extension (FDnet)
(optional)
Station
Addresse
s (max.)
Line cards
integrated
Qty.
Loops
integrate
d
Loop
extensions
Card cage Line cards (FDnet/C-NET)
FC2020 252 1 2 loops +2 loops -- -- --
FG2020 252 -- -- --
1 card cage
with 2 slots
Max. 2 Max. 8 loops
FC2030 756 1 2 loops +2 loops
1 card cage
with 2 slots
Max. 2 Max. 8 loops
FC2040 504 2 4 loops +4 loops -- -- --
FC2060 1512 2 4 loops +4 loops
1 card cage
with 5 slots
Max. 5 Max 20 loops
FC2080 5000 -- -- --
Max. 7 card
cages each
with 5 slots
Max. 30 Max. 120 loops
Table 12: Overview of line distribution FDnet
Properties
Each FDnet line card has two line drivers, which each support two loops
or four partial loops.
A loop can be divided into two partial loops on the integrated line card with the
loop extension (FDnet).
The additional line cards (FDnet/C-NET) FCL2001-A1 have the loop extension
permanently built-in by default.
L1 L2L1a L2a
Line card
(FDnet/C-NET)
FCL2001

Table of Contents