Planning an FDnet detector line
7
78 | 242
Device Type Number AK ΣAK RK ΣRK MK ΣMK
Neural radio detector
(SWING)
FDOOT271 1 0 0
Radio smoke detector DOW1171 1 1 1
Manual call point with radio
base
SMF6120
SMF121
1 1 1
Radio manual call point FDM273 1 1 1
VESDA Laser Focus VLF-250/500 1 3 3
Support for ASD system FDCC221 1 3 3
↑ Floor repeater terminal /
↑ floor repeater display
without external supply
FT2010
FT2011
1 20 160
Floor repeater terminal /
display with external supply
FT2010
FT2011
1 20 20
Mimic display driver,
without external supply
FT2001 1 40 100
Mimic display driver, with
external supply
FT2001 1 40 40
Total
Table 20: AK, RK and MK of the FDnet devices
1
n = Number of connected radio detectors
2
Check with your country representative that this detector is approved for FDnet in
your country.
You will find detailed information on functions, connection factors and device
compatibility in document 'List of compatibility'.