Planning detector lines
AnalogPLUS detector line
7
92 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
External supply for line devices
The line card (AnalogPLUS) has no supply output for line devices. A separate
power supply may need to be provided.
Supported detectors
The line card (AnalogPLUS) supports the same recording peripheral equipment
as the corresponding AlgoRex line plug-in modules E3M110, E3M111, K3M111:
Optical smoke detectors: DO113x, OP620A, OP320A
Multi-sensor smoke detectors: DOT1131, OH620A, OH320A
Heat detectors: DT113x, HI32xA, HI62xA
Flame detectors: DF119x
Manual call points: DM113x, DMA1133, MT320A
Input modules: DC1131, EB322A
Output modules: DC1134, DC1136, AB322A
Input/output modules: DC1192, CB320A, ABI322A
Collective detectors above DC1192
Collective Ex detectors above DC1192 and SB3
SynoLINE300C above CB320A
DC1135
is no longer supported.
Additional documentation
You will find detailed information on the line card (AnalogPLUS) in the
008837 product data.
You will find detailed information on device compatibility in the 'List of
compatibility'.
You will find the information on the AnalogPLUS line devices in the
corresponding AlgoRex documents.
You will find information about key detector figures in the AlgoRex document
Guidelines 001508.
You will find information on modernization and migration in the documents
A6V10323158 'Modernizing fire detection installations with multiple protocol
detectors' and in the configuration 009078 in the chapter 'AlgoRex /
SIGMASYS data migration'.
You will find information about configuration and commissioning in documents
009052 and 009078.
See chapter 'Applicable documents'.