EasyManua.ls Logo

Siemens SIPROTEC 7SJ80

Siemens SIPROTEC 7SJ80
562 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[ueb-einph-hochimpedanz-020926-rei, 1, en_US]
Figure 2-38 Ground fault protection according to the high-impedance principle
Function of the High-Impedance Principle
The high-impedance principle is explained on the basis of a grounded transformer winding.
No zero sequence current will flow during normal operation, i.e. the neutral point current is Ι
SP
= 0 and the
phase currents are 3 Ι
0
= Ι
A
+ Ι
B
+ Ι
C
= 0.
In case of an external ground fault (left in Figure 2-39), whose fault current is supplied via the grounded
neutral point, the same current flows through the transformer neutral point and the phases. The corre-
sponding secondary currents (all current transformers have the same transformation ratio) compensate each
other; they are connected in series. Across resistor R only a small voltage is generated. It originates from the
inner resistance of the transformers and the connecting cables of the transformers. Even if any current trans-
former experiences a partial saturation, it will become low-ohmic for the period of saturation and creates a
low-ohmic shunt to the high-ohmic resistor R. Thus, the high resistance of the resistor also has a stabilizing
effect (the so-called resistance stabilization).
[ueb-einph-hochimpedanz2-020926-rei, 1, en_US]
Figure 2-39 Principle of ground fault protection according to the high-impedance principle
When a ground fault occurs in the protected zone Figure 2-39 right), there is always a neutral point current Ι
SP
.
The grounding conditions in the rest of the network determine how strong a zero sequence current from the
system is. A secondary current which is equal to the total fault current tries to pass through the resistor R.
Since the latter is high-resistive, a high voltage emerges immediately. Therefore, the current transformers get
saturated. The RMS voltage across the resistor approximately corresponds to the knee-point voltage of the
current transformers.
Resistance R is sized such that, even with the very lowest ground fault current to be detected, it generates a
secondary voltage, which is equal to half the saturation voltage of current transformers (see also notes on
"Dimensioning" in Subsection 2.5.4 Setting Notes).
Functions
2.5 Single-Phase Overcurrent Protection
114 SIPROTEC 4, 7SJ80, Manual
E50417-G1140-C343-A8, Edition 12.2017

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ80

Related product manuals