No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
1120 Flt Locator: Distance [%]
to fault (d[%] =)
Fault
Locator
VI ON
OFF
15
1
20 4 No
1122 Flt Locator: Distance to
fault (dist =)
Fault
Locator
VI ON
OFF
15
1
22 4 No
1123 Fault Locator Loop AG (FL
Loop AG)
Fault
Locator
OUT * On * LED BO
1124 Fault Locator Loop BG (FL
Loop BG)
Fault
Locator
OUT * On * LED BO
1125 Fault Locator Loop CG (FL
Loop CG)
Fault
Locator
OUT * On * LED BO
1126 Fault Locator Loop AB (FL
Loop AB)
Fault
Locator
OUT * On * LED BO
1127 Fault Locator Loop BC (FL
Loop BC)
Fault
Locator
OUT * On * LED BO
1128 Fault Locator Loop CA (FL
Loop CA)
Fault
Locator
OUT * On * LED BO
1132 Fault location invalid
(Flt.Loc.invalid)
Fault
Locator
OUT * On * LED BO
1201 >BLOCK 64 (>BLOCK 64) Sens. Gnd
Fault
SP On
Of
f
* * LED BI BO 15
1
10
1
1 Yes
1202 >BLOCK 50Ns-2 (>BLOCK
50Ns-2)
Sens. Gnd
Fault
SP On
Of
f
* * LED BI BO 15
1
10
2
1 Yes
1203 >BLOCK 50Ns-1 (>BLOCK
50Ns-1)
Sens. Gnd
Fault
SP On
Of
f
* * LED BI BO 15
1
10
3
1 Yes
1204 >BLOCK 51Ns (>BLOCK
51Ns)
Sens. Gnd
Fault
SP On
Of
f
* * LED BI BO 15
1
10
4
1 Yes
1207 >BLOCK 50Ns/67Ns (>BLK
50Ns/67Ns)
Sens. Gnd
Fault
SP On
Of
f
* * LED BI BO 15
1
10
7
1 Yes
1211 50Ns/67Ns is OFF (50Ns/
67Ns OFF)
Sens. Gnd
Fault
OUT On
Of
f
* * LED BO 15
1
11
1
1 Yes
1212 50Ns/67Ns is ACTIVE
(50Ns/67Ns ACT)
Sens. Gnd
Fault
OUT On
Of
f
* * LED BO 15
1
11
2
1 Yes
1215 64 displacement voltage
pick up (64 Pickup)
Sens. Gnd
Fault
OUT * On
Off
* LED BO 15
1
11
5
2 Yes
1217 64 displacement voltage
element TRIP (64 TRIP)
Sens. Gnd
Fault
OUT * On m LED BO 15
1
11
7
2 Yes
Functions, Settings, Information
F.3 Information List
SIPROTEC 4, 7SJ80, Manual 515
E50417-G1140-C343-A8, Edition 12.2017