No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
2693 67/67-TOC Phase B picked
up (67 B picked up)
67 Direct.
O/C
OUT * On
Off
* LED BO 63 52 2 Yes
2694 67/67-TOC Phase C picked
up (67 C picked up)
67 Direct.
O/C
OUT * On
Off
* LED BO 63 53 2 Yes
2695 67N/67N-TOC picked up
(67N picked up)
67 Direct.
O/C
OUT * On
Off
* LED BO 63 54 2 Yes
2696 67/67N TRIP (67/67N
TRIP)
67 Direct.
O/C
OUT * On m LED BO 63 55 2 Yes
2697 67-3 picked up (67-3
picked up)
67 Direct.
O/C
OUT * On
Off
* LED BO
2698 67N-3 picked up (67N-3
picked up)
67 Direct.
O/C
OUT * On
Off
* LED BO
2699 67-3 Time Out (67-3 Time
Out)
67 Direct.
O/C
OUT * * * LED BO
2700 67N-3 Time Out (67N-3
Time Out)
67 Direct.
O/C
OUT * * * LED BO
2701 >79 ON (>79 ON) 79M Auto
Recl.
SP On
Of
f
* * LED BI BO 40 1 1 Yes
2702 >79 OFF (>79 OFF) 79M Auto
Recl.
SP On
Of
f
* * LED BI BO 40 2 1 Yes
2703 >BLOCK 79 (>BLOCK 79) 79M Auto
Recl.
SP On
Of
f
* * LED BI BO 40 3 1 Yes
2711 >79 External start of
internal A/R (>79 Start)
79M Auto
Recl.
SP * On
Off
* LED BI BO
2715 >Start 79 Ground
program (>Start 79 Gnd)
79M Auto
Recl.
SP * On * LED BI BO 40 15 2 Yes
2716 >Start 79 Phase program
(>Start 79 Ph)
79M Auto
Recl.
SP * On * LED BI BO 40 16 2 Yes
2720 >Enable 50/67-(N)-2
(override 79 blk) (>Enable
ANSI#-2)
P.System
Data 2
SP On
Of
f
* * LED BI BO 40 20 1 Yes
2722 >Switch zone sequence
coordination ON (>ZSC
ON)
79M Auto
Recl.
SP On
Of
f
* * LED BI BO
2723 >Switch zone sequence
coordination OFF (>ZSC
OFF)
79M Auto
Recl.
SP On
Of
f
* * LED BI BO
2730 >Circuit breaker READY
for reclosing (>CB Ready)
79M Auto
Recl.
SP On
Of
f
* * LED BI BO 40 30 1 Yes
Functions, Settings, Information
F.3 Information List
SIPROTEC 4, 7SJ80, Manual 525
E50417-G1140-C343-A8, Edition 12.2017