No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
5159 46-2 picked up (46-2
picked up)
46 Negative
Seq
OUT * On
Off
* LED BO 70 13
8
2 Yes
5165 46-1 picked up (46-1
picked up)
46 Negative
Seq
OUT * On
Off
* LED BO 70 15
0
2 Yes
5166 46-TOC picked up (46-
TOC pickedup)
46 Negative
Seq
OUT * On
Off
* LED BO 70 14
1
2 Yes
5170 46 TRIP (46 TRIP) 46 Negative
Seq
OUT * On m LED BO 70 14
9
2 Yes
5171 46 Disk emulation picked
up (46 Dsk pickedup)
46 Negative
Seq
OUT * * * LED BO
5203 >BLOCK 81O/U (>BLOCK
81O/U)
81 O/U
Freq.
SP On
Of
f
* * LED BI BO 70 17
6
1 Yes
5206 >BLOCK 81-1 (>BLOCK
81-1)
81 O/U
Freq.
SP On
Of
f
* * LED BI BO 70 17
7
1 Yes
5207 >BLOCK 81-2 (>BLOCK
81-2)
81 O/U
Freq.
SP On
Of
f
* * LED BI BO 70 17
8
1 Yes
5208 >BLOCK 81-3 (>BLOCK
81-3)
81 O/U
Freq.
SP On
Of
f
* * LED BI BO 70 17
9
1 Yes
5209 >BLOCK 81-4 (>BLOCK
81-4)
81 O/U
Freq.
SP On
Of
f
* * LED BI BO 70 18
0
1 Yes
5211 81 OFF (81 OFF) 81 O/U
Freq.
OUT On
Of
f
* * LED BO 70 18
1
1 Yes
5212 81 BLOCKED (81
BLOCKED)
81 O/U
Freq.
OUT On
Of
f
On
Off
* LED BO 70 18
2
1 Yes
5213 81 ACTIVE (81 ACTIVE) 81 O/U
Freq.
OUT On
Of
f
* * LED BO 70 18
3
1 Yes
5214 81 Under Voltage Block
(81 Under V Blk)
81 O/U
Freq.
OUT On
Of
f
On
Off
* LED BO 70 18
4
1 Yes
5232 81-1 picked up (81-1
picked up)
81 O/U
Freq.
OUT * On
Off
* LED BO 70 23
0
2 Yes
5233 81-2 picked up (81-2
picked up)
81 O/U
Freq.
OUT * On
Off
* LED BO 70 23
1
2 Yes
5234 81-3 picked up (81-3
picked up)
81 O/U
Freq.
OUT * On
Off
* LED BO 70 23
2
2 Yes
Functions, Settings, Information
F.3 Information List
SIPROTEC 4, 7SJ80, Manual 529