152 097-55501-01 Issue 6 – June 2003
1
TimeHub 5500 System Guide
23 Use the Edit Equipment command to set the gateway IP address.
ED-EQPT:::<ctag>:::IPGATEX=a;
a = a.a.a.a, where each is an independent value of 0 to 255
Note: To verify the parameter, use the Retrieve Equipment command.
RTRV-EQPT:::<ctag>:::PARAMETER=IPGATEX;
24 Use the Edit Equipment command to set the element manager IP address.
ED-EQPT:::<ctag>:::IPEM1X=a;
a = a.a.a.a, where each is an independent value of 0 to 255
Note: To verify the parameter, use the Retrieve Equipment command.
RTRV-EQPT:::<ctag>:::PARAMETER=IPEM1X;
25 Use the Edit Equipment command to set the local manager IP address.
ED-EQPT:::<ctag>:::IPLM1X=a;
a = a.a.a.a, where each is an independent value of 0 to 255
Note: To verify the parameter, use the Retrieve Equipment command.
RTRV-EQPT:::<ctag>:::PARAMETER=IPLM1X;
26 Use the Edit Equipment command to specify the port number for commands and
responses.
ED-EQPT:::<ctag>:::PORTCMDSX=a;
a = 5001 to 20000
Notes:
1. To verify the parameter, use the Retrieve Equipment command.
RTRV-EQPT:::<ctag>:::PARAMETER=PORTCMDSX;
2. If AOMERGE was set to Y, automatic output messages, and commands and responses
will be combined on this port.
Procedure 4-9. System Configuration (Cont’d)
Step Action