206
Remote Control
Res:Set:Current HV,2.2
Res:Set:Current LV,8.9
Dem:Set:Phase HV,2
RemoteToLocal
After sending all the settings, a
Meas:Start
will start the demagnetization process. Further
Meas:State
Has to be used to find out in which state the device currently is. For the demagnetization process
the state flow will typically look like
Standby Initializing Charging Measuring Discharging
DemagAnalyzing Initializing Charging Discharging
DemagAnalyze
DemagCycleInit
In the state DemagCycleInit the system decides whether the transformer is still
magnetized (next cycle) or already demagnetized (no more cycles).
(Not Demag.) Initializing Charging Discharging
DemagCycleInit
(Demag.) Reset Standby
One can observe the current measured values during the whole process using
Dem:Meas?
If a measuring process aborts unexpectedly or the system state is Reset or Interlock, one
can get an error message using
Meas:Error