Meas:Continue
is issued. The sequence can be stopped anytime by sending
Meas:Stop
One can observe the current measured values during the whole process using
Res:Meas:R?
Res:Meas:U?
Res:Meas:I?
Res:Meas:T?
Temp:Values?
Recorded values (auto or manual) can be obtained using
Res:Data:R?
Res:Data:U?
Res:Data:I?
Res:Data T?
If a measuring process aborts unexpectedly or the system state is Reset or Interlock, one
can get an error message using
Meas:Error
22.4.2 Tap Changer Control
A remote controlled tap changer can be operated using
TC:Move Up ¦ Down
This operation is only valid if the system state is either Measuring or Standby. Further only an
On-Load Tap Changer could be operated during Measuring. NEVER operate an Off-Load Tap
Changer during Measuring. An Off-Load Tap Changer must be operated ALWAYS during
Standby. After issuing a TC:Move command the Tap Changer Feedback will be set to 0. When
the Tap Changer movement completed, the feedback will be set to 1. This status can be obtained
using
TC:Feedback?