Heat Run - Temperature Rise
Temperature measurements
continue while the phase 2 timer
counts down.
When the countdown is complete,
click OK
Click Continue to switch automatic
from Temperature Rise to Cooling
Curve application.
When the rated current injection is
switched off, press Start Timer.
Then connect immediately the
measurement clamps to the
transformer and press Start Meas
Temperature rise tests cannot be run unless one
temperature position is defined in setup.