0…20 mA bipolar Diagnostics dec. hex.
Current value I
M
= (dec. value × 7.234 × 10
-4
) mA
23.70298 mA Overflow 32767 7FFF
23.51852 mA atDIA
Measured value out of
range ON
32512 7F00
23.517795 mA out of range 32511 7EFF
23,2060 mA at DIA
Measured value out of
range Off
32080 7D50
20.000723 mA 27649 6C01
20.000000 mA nominal range 27648 6C00
10.0000 mA 13824 3600
0.0007234 mA 1 0001
0.000000 mA 0 0000
-0.1 mA Underflow atDIA
Overflow/underflow,
OUFL Off
0 000×
< -0.2 mA at DIA
Overflow/underflow,
OUFL ON
0 000×