Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
170
4…20 mA bipolar Diagnostics dec. hex.
Current value I
M
= (dec. value × 5,787 × 10
-4
) mA
22.96238 mA Overflow 32767 7FFF
22.81481 mA atDIA
Measured value out of
range ON
32512 7F00
22.814236 mA out of range 32511 7EFF
22,56482 mA at DIA
Measured value out of
range Off
32080 7D50
20.000579 mA 27649 6C01
20.000000 mA nominal range 27648 6C00
… … …
12.0000 mA 13824 3600
… … …
4.0005787 mA 1 0001
4.000000 mA 0 0000
3.999421 mA Underflow -1 FFFF
1.5567 mA atDIA
Measured value out of
range
Off
-4222 EEBA
1.185185 -4864 ED00
1,184606 mA Underflow at DIA
Measured value out of
range ON
-4865 ECFF
0.0000 mA -6912 E500