Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
172
0…10 V bipolar Diagnostics dec. hex.
Voltage value U
M
= (dec. value/ 16 × 5,787 × 10
-3
) V
11,8460 V Overflow 2047 × 16 7FF0
11,7592 V atDIA
Measured value out of
range ON
2032 × 16 7F00
11.7535 V out of range 2031 × 16 7EF0
11,6030 V at DIA
Measured value out of
range Off
2005 × 16 7D50
10.0058 V 1729 × 16 6C10
10.000000 V nominal range 1728 × 16 6C00
… … …
5.0000 V 864 × 16 3600
… … …
0.000578 V 1 × 16 0010
0.00000 V 0 0000
-0,050 V Underflow atDIA
Overflow/underflow,
OUFL Off
0 0000
< -0.100 V at DIA
Overflow/underflow,
OUFL ON
0 0000