173
2020/09
0…20 mA bipolar Diagnostics dec. hex.
Current value I
M
= (dec. value/16 × 0,01157) mA
23.6921 mA Overflow 2047 × 16 7FF0
23.51852 mA atDIA
Measured value out of
range ON
2032 × 16 7F00
23.5069 mA out of range 2031 × 16 7EF0
23,2060 mA at DIA
Measured value out of
range Off
2005 × 16 7D50
20.0116 mA 1729 × 16 6C10
20.000000 mA nominal range 1728 × 16 6C00
10.0000 mA 864 × 16 3600
0.01157 mA 1 × 16 0010
0,0000 mA 0 0000
-0.1 mA Underflow atDIA
Overflow/underflow,
OUFL Off
0 0000
-0.2 mA at DIA
Overflow/underflow,
OUFL ON
0 0000

Table of Contents