- 10.001 V out of range -10001 D8EF
-10.250 V atDIA
Measured value out of
range Off
-10250 D7F6
-10.500 V at DIA
Measured value out of
range
ON
-10500 D6FC
-10.501 V Underflow -10501 D6FB
-10.999 V atDIA
Overflow/underflow,
OUFL Off
-10999 D509
-11,000 V at DIA
Overflow/underflow,
OUFL
ON
-11000 D508
0…10 V unipolar Diagnostics dec. hex.
Voltage value U
M
= (dec. value × 0,001) V
11,000 V Overflow atDIA
Overflow/underflow,
OUFL ON
11000 2AF8
10,999 V at DIA
Overflow/underflow,
OUFL Off
10999 2AF7
10.501 V atDIA
Measured value out of
range ON
10501 2905
10,500 V out of range 10500 2904
10,250 V at DIA
Measured value out of
range Off
10250 280A
10.001 V 10001 2711
10.000 V nominal range 10000 2710
5.000 V 5000 1388
0.001 V 1 0001
0.000 V 0 0000
- 0,05 V Underflow atDIA
Overflow/underflow,
OUFL Off
0 0000
< -0.10 V at DIA
Overflow/underflow,
OUFL ON
0 0000