177
2020/09
0…20 mA unipolar Diagnostics dec. hex.
Current value I
M
= (dec. value × 0,001) mA
22.000 mA Overflow atDIA
Overflow/underflow,
OUFL ON
22000 55F0
21,999 mA at DIA
Overflow/underflow,
OUFL Off
21999 55EF
21.001 mA atDIA
Measured value out of
range ON
21001 5209
21.000 mA out of range 21000 5208
20,500 mA at DIA
Measured value out of
range Off
20500 5014
20.001 mA 20001 4E21
20.000 mA nominal range 20000 4E20
… … …
10.000 mA 10000 2712
… … …
0.001 mA 1 0001
0.0000 mA 0 0000
-0.1 mA Underflow atDIA
Overflow/underflow,
OUFL
Off
0 0000
< -0.2 mA at DIA
Overflow/underflow,
OUFL ON
0 0000