Analog Input Modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
178
4…20 mA unipolar Diagnostics dec. hex.
Current value I
M
= (dec. value × 0,001) mA
22.000 mA Overflow atDIA
Overflow/underflow,
OUFL ON
22000 55F0
21,999 mA at DIA
Overflow/underflow,
OUFL Off
21999 55EF
21.001 mA atDIA
Measured value out of
range ON
21001 5209
21.000 mA out of range 21000 5208
20,500 mA at DIA
Measured value out of
range Off
20500 5014
20.001 mA 20001 4E21
20.000 mA nominal range 20000 4E20
… … …
12.000 mA 12000 2EE0
… … …
4.001 mA 4001 0FA1
4.000 mA 4000 0FA0
3.999 mA out of range 3999 0F9F
3.800 mA atDIA
Measured value out of
range
Off
3800 0ED8
3.600 mA at DIA
Measured value out of
range
ON
3600 0E10
3.599 mA Underflow 3599 0E0F
2.001 mA atDIA
Wire break Off
2001 07D1
2,000 mA at DIA
Wire break ON
2000 07D0
0.000 mA 0000 0000