12-bit-representation (left-justified)
Measurement range, Pt 200...850 °C Transmitted value
Pt100, Pt200, Pt500, Pt1000 dec. hex.
temperature T
M
= (dec. value/16 × 0,5) °C
101.0 % 858,5 °C atDIA
Measured value out of
range ON
1700 × 16 6A4×
100.5 % 854,2 °C atDIA
Measured value out of
range Off
1700 × 16 6A4×
> 100,0 % 850.0 °C Nominal value 1700 × 16 6A4×
0.5 °C 1 × 16 001x
0.0 % 0 °C 0 000×
-0.5 °C -1 × 16 FFFx
-100 % -200.0 °C -400 × 16 E70×
-100.5 % -201,0 °C atDIA
Measured value out of
range Off
-400 × 16 E70×
-101.0 % -202,0 °C at DIA
Measured value out of
range ON
-400 × 16 E70×
Measurement range, Pt 200...150 °C Transmitted value
Pt100, Pt200, Pt500, Pt1000 dec. hex.
temperature T
M
= (dec. value/16 × 0,1) °C
101.0 % 151,50 °C atDIA
Measured value out of
range
ON
1500 × 16 5DC×
100.5 % 150,80 °C atDIA
Measured value out of
range Off
1500 × 16 5DC×
> 100,0 % 150.00 °C Nominal value 1500 × 16 5DC×
0.1 °C 1 001×
0.0 % 0 °C 0 000×
-0.1 °C -1 FFF×
-100 % -200.0 °C -2000 × 16 830×
-100.5 % -201,0 °C atDIA
Measured value out of
range Off
-2000 × 16 830×
-101.0 % -202,0 °C at DIA
Measured value out of
range
ON
-2000 × 16 830×