189
2020/09
Measurement range, Ni -60…250 °C Transmitted value
Ni100, Ni1000, Ni100TK5000 dec. hex.
temperature T
M
= (dec. value/16 × 0,5) °C
101.0 % 252,50 °C atDIA
Measured value out of
range
ON
500 × 16 1F4×
100.5 % 251,20 °C atDIA
Measured value out of
range OFFOFF
500 × 16 1F4×
> 100,0 % 250.00 °C Nominal value 500 × 16 1F4×
… … … …
0.5 °C 1 × 16 001×
0.0 % 0 °C 0 000×
-0.5 °C -1 × 16 FFF×
…
-100 % -60.00 °C -120 × 16 F88x
-100.5 % -60,30 °C atDIA
OffOFF
-120 × 16 F88×
-101.0 % -60,60 °C at DIA
Measured value out of
range ON
-120 × 16 F88×
Measurement range, Ni -60…150 °C Transmitted value
Ni100, Ni1000 dec. hex.
temperature T
M
= (dec. value/16 × 0,1) °C
101.0 % 151,50 °C atDIA
Measured value out of
range ON
1500 ×16 5DC×
100.5 % 150,70 °C atDIA
Measured value out of
range Off
1500 ×16 5DC×
> 100,0 % 150.0 °C Nominal value 1500 ×16 5DC×
… … … …
0.1 °C 1 × 16 001×
0.0 % 0 °C 0 000×
-0.1 °C -1 × 16 FFF×
…
-100 % -60.00 °C -600 × 16 DA8×
-100.5 % -60,30 °C atDIA
Measured value out of
range
Off
-600 × 16 DA8×
-101.0 % -60,6 0°C at DIA
Measured value out of
range ON
-600 × 16 DA8×